Quick Start Guide
11
January 2015
Analog input (AI) function blocks
The AI block processes field device measurements and makes the outputs
available to other function blocks. The output value of the AI block is in
engineering units and contains a status indicating the quality of the
measurements. Use the channel number to define the variable that the AI block
processes. At a minimum, verify the parameters of the AI blocks in Ta bl e 2.
Note
To make changes to the AI block, the BLOCK_MODE (TARGET) must be set to OOS (out of service).
Once the changes are made, return the BLOCK_MODE TARGET to AUTO.
Table 2. AI Block Parameters
(1)
1. Configure one AI Block for each desired measurement.
Parameter Comments
CHANNEL
Choices:
Sensor 1 – 8
Differential Sensors 1 – 4
Body Temperature
L_TYPE For most measurements, set to “DIRECT”
XD_SCALE
Set the desired measurement range and units. Units must be one of the
following:
mV
Ohms
°C
°F
°R
K
mA
OUT_SCALE For “DIRECT” L_TYPE, set OUT_SCALE to match XD_SCALE
HI_HI_LIM
LO_LO_LIM
HI_LIM
LO_LIM
Process alarms.
Must be within the range defined by “OUT_SCALE”
Vista de página 10