January 2015
16
Quick Start Guide
IA ATEX FISCO Intrinsic Safety
Certificate: Baseefa09ATEX0093X
Standards: EN 60079-0:2012, EN60079-11:2012
Markings: II 1 G Ex ia IIC T4 Ga (-50 °C
T
a
+60 °C) when installed per drawing
00848-4406
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a degree of
protection of at least IP20. Non-metallic enclosures must be suitable to
prevent electrostatic hazards and light alloy or zirconium enclosures must be
protected from impact and friction when installed.
2. The equipment is note capable of withstanding the 500 V insulation test
required by EN 60079-11:2012, clause 6.3.13. This must be taken into
account when installing the equipment.
N1 ATEX Type n (with enclosure)
Certificate: Baseefa09ATEX0095X
Standards: EN 60079-0:2006, EN60079-15:2005
Markings: II 3 G Ex nA nL IIC T5(-40 °C
T
a
+65 °C)
Special Conditions for Safe Use (X):
1. Provision must be made, external to the apparatus, to ensure the rated
voltage of the apparatus supply is not exceeded by transient disturbances of
more than 40%.
2. The electrical circuit is connected directly to earth; this must be taken into
account when installing the apparatus.
Table 6. Entity Parameters
Fieldbus
(input)
Sensor field terminal
(output)
U
i
= 30 V U
O
= 12.5 V
I
i
= 300 mA I
O
= 4.8 mA
P
i
= 1.3 W P
O
= 15 mW
C
i
= 2.1 nF C
O
= 1.2 μF
L
i
= 0 L
O
= 1 H
Table 7. Entity Parameters
FISCO
(input)
Sensor field terminal
(output)
U
i
= 17.5 V U
O
= 12.5 V
I
i
= 380 mA I
O
= 4.8 mA
P
i
= 5.32 W P
O
= 15 mW
C
i
= 2.1 nF C
O
= 1.2 μF
L
i
= 0 L
O
= 1 H